Materials reqd- 1. Data Sheet , 2. Multimeter , 3. Pressure calibrator , 4. Hart Comm , 5. Tester & Slide range
PROCEDURES...
1. Force the transmitter from DCS/PLC if it comes under any tripping circuit.
2. Connect the HART Communicator & note down the LRV , URV , TAG , UNIT , PV , DAMPING etc.
3. Isolate the transmitter from process.
4. Release both side pressure & drain the low and high side liquid by drain valve.
5. Connect pressure calibrator to the high side, keeping low side open to atmospher...
Continue reading ...